dc.contributor.authorFlores Nieves, Ramon H.
dc.contributor.authorPérez Dumeng, Luis A.
dc.date.accessioned2022-04-18T14:10:21Z
dc.date.available2022-04-18T14:10:21Z
dc.date.issued1994-12
dc.identifier.citationFlores Nieves, R. H. & Pérez Dumeng, L. A. (1994). Análisis del sistema de protección de IPR Pharmaceuticals, Inc, Revista de la Universidad Politécnica de Puerto Rico, 4(2), 191-221.en_US
dc.identifier.urihttp://hdl.handle.net/20.500.12475/1473
dc.descriptionVolumen 4, Número 2, Diciembre 1994en_US
dc.description.abstractAnalysis of the electrical protection system of IPR Pharmaceuticals This study is based on the electrical distribution system of a pharmaceutical plant. The purpose of the study is to investigate why the low voltage switchgear 800A circuit breaker feeding a motor control center (MCC) tripped to clear a fault that occurred at a 277V street light pole. We also want to know why the preceding 20A branch circuit breaker and the 60A main breaker feeding the panel board did not trip. As a consequence of this fault the steam boiler was shut down.The one-line diagran of the electrical system of the plant and the circuit breakers sequence connections are shown. To verify the existing coordination problem we plotted the time-current characteristic curves of die circuit breakers involved and made sure there was no overlapping between the breaker's curves. An overlapping means that either breaker or all of them will trip at the same time when a fault occurs. After studying and analyzing die fault we suggest two alternatives to solve this breaker coordination problem: changing the settings of the breakers to their maximum, and to replace one breaker for another with the ground fault protection option; however, we would have to change settings to the remainder breakers.en_US
dc.language.isoesen_US
dc.publisherPolytechnic University of Puerto Ricoen_US
dc.relation.ispartofRevista de la Universidad Politécnica de Puerto Rico;
dc.relation.haspartSan Juanen_US
dc.subject.lcshElectric power systems--Protectionen_US
dc.subject.lcshPolytechnic University of Puerto Rico--Undergraduates--Researchen_US
dc.titleAnálisis del sistema de protección de IPR Pharmaceuticals, Incen_US
dc.typeArticleen_US
dc.rights.holderEsta Junta Editorial y la Universidad Politécnica de Puerto Rico hacen constar y reconoce que los autores de los artículos, obras literarias y artísticas publicadas en esta Revista Politechnê, se reservan enteramente los derechos de autor y de publicación de los mismos para los efectos de cualquier ventualidad literaria, publicitaria o de cualquier índole.en_US