Mostrar el registro sencillo del ítem
Análisis del sistema de protección de IPR Pharmaceuticals, Inc
dc.rights.license | All rights reserved | en_US |
dc.contributor.author | Flores Nieves, Ramon H. | |
dc.contributor.author | Pérez Dumeng, Luis A. | |
dc.date.accessioned | 2022-04-18T14:10:21Z | |
dc.date.available | 2022-04-18T14:10:21Z | |
dc.date.issued | 1994-12 | |
dc.identifier.citation | Flores Nieves, R. H. & Pérez Dumeng, L. A. (1994). Análisis del sistema de protección de IPR Pharmaceuticals, Inc, Revista de la Universidad Politécnica de Puerto Rico, 4(2), 191-221. | en_US |
dc.identifier.uri | http://hdl.handle.net/20.500.12475/1473 | |
dc.description | Volumen 4, Número 2, Diciembre 1994 | en_US |
dc.description.abstract | Analysis of the electrical protection system of IPR Pharmaceuticals This study is based on the electrical distribution system of a pharmaceutical plant. The purpose of the study is to investigate why the low voltage switchgear 800A circuit breaker feeding a motor control center (MCC) tripped to clear a fault that occurred at a 277V street light pole. We also want to know why the preceding 20A branch circuit breaker and the 60A main breaker feeding the panel board did not trip. As a consequence of this fault the steam boiler was shut down.The one-line diagran of the electrical system of the plant and the circuit breakers sequence connections are shown. To verify the existing coordination problem we plotted the time-current characteristic curves of die circuit breakers involved and made sure there was no overlapping between the breaker's curves. An overlapping means that either breaker or all of them will trip at the same time when a fault occurs. After studying and analyzing die fault we suggest two alternatives to solve this breaker coordination problem: changing the settings of the breakers to their maximum, and to replace one breaker for another with the ground fault protection option; however, we would have to change settings to the remainder breakers. | en_US |
dc.language.iso | es | en_US |
dc.publisher | Polytechnic University of Puerto Rico | en_US |
dc.relation.ispartof | Revista de la Universidad Politécnica de Puerto Rico; | |
dc.relation.haspart | San Juan | en_US |
dc.subject.lcsh | Electric power systems--Protection | en_US |
dc.subject.lcsh | Polytechnic University of Puerto Rico--Undergraduates--Research | en_US |
dc.title | Análisis del sistema de protección de IPR Pharmaceuticals, Inc | en_US |
dc.type | Article | en_US |
dc.rights.holder | Esta Junta Editorial y la Universidad Politécnica de Puerto Rico hacen constar y reconoce que los autores de los artículos, obras literarias y artísticas publicadas en esta Revista Politechnê, se reservan enteramente los derechos de autor y de publicación de los mismos para los efectos de cualquier ventualidad literaria, publicitaria o de cualquier índole. | en_US |
Ficheros en el ítem
Este ítem aparece en la(s) siguiente(s) colección(ones)
-
Revista Politechnê
Revista multidisciplinaria de la Universidad Politécnica de Puerto Rico (Vol. 1 | Núm. 1 | Junio 1991 - Vol. 22 | Núm. 1 | 2024